The ezPACTM SA300
Series Power Intelligence Unit is an advanced power analysis and
control device unmatched in the utility and industrial environments.
The SATEC ezPACTM
SA300 Series are a fusion of many intelligent electronic devices
(IED) combined into one single powerful unit. The SATEC ezPACTM SA300
Series unite Distributed Fault-Recording, Sequence of Events (SOE),
Revenue Metering, Power Quality, Back up to Protection equipment and
control devices to provide a complete solution for substation and
industrial automation.
The unique modular expansion chassis of the SATEC ezPACTM SA300
Series assures the capability of meeting the needs of today and the
future by selecting different plug-in options for multiple
applications. The ezPACTM
allows a relatively low cost upgrade to be accomplished with just
minimal panel and wiring changes. Modular I/O design lets you order a
custom-made product according to your needs.
Upgradeable Firmware
The SATEC SA300 uses flash memory for storing device firmware
that allows future upgrading of the device without replacing any
hardware component. You no longer have to replace EPROM and remove from
service. The new features can be easily added to your device by simply
replacing the firmware through a local RS-232 port or Ethernet port.
Substation
Automation Upgrade
The SATEC ezPACTM
SA300 Power Intelligence Unit is an ideal cost effective means of
automating an electrical substation. The SATEC ezPACTM can be
installed at a fraction of the cost and time involved in replacing
protection relays. By adding one SATEC ezPACTM Model
on each feeder circuit, ALL the information needed for substation
automation is provided. The SATEC ezPACTM SA300
extends the life expectancy of electromechanical relays for many years
to come by providing “INFORMATION” lacking in these highly
reliable devices without interfering in the protection scheme.
The SA300 combines in a single
enclosure:
|
|
|
Distributed Fault Recording – Functions include true digital fault recording, sequence of
event recording, and disturbance recording of four current channels for up to 150 Amps of fault currents (30X). Four AC voltage
channels and DC measurement input channels are also included. Multiple ezPACTM can
cross trigger for up to 20 cycles of pre-fault information for
distributed recording. Fault information can be exported to optional
COMTRADE format via PAS software.
|
|
Precise Sequence-of-Events Recorder
(SOE) - Designed for a electrical utility
substation or plant environment to record contact openings and closing
of field devices such as electromechanical and microprocessor
controlled relays.16 digital inputs are provided and can easily expand
up to a total of 48 digital inputs (wet or dry type) with a 1 mSec time
resolution between events. |
|
Power Quality Analyzer - Advanced power quality monitoring reporting as per IEEE 1159
classification. Report by exception with programmable thresholds and
hysteresis, ready-for-use reports; transients, impulses, sags/swells,
interruptions, inter-harmonics as per IEEE519, frequency variations,
volts unbalance. |
|
High Speed Sampling- The utilization of the latest DSP technology and
the innovative data concept allow very long recording periods without
compromising the high level of accuracy. Simultaneous
sampling with individual A/D conversions assures no phase differential
for 12-channels of AC, one VDC and digital inputs recording. Selectable
simultaneous AC recording rate of 32, 64 and 128 samples per cycle;
over 3 min of continuous recording with a 5-Mbyte onboard
expandable memory. |
|
Long Term Recording - For data logging & trending, internal diagnostics events,
control events and I/O operations.
|
|
Fast Data Logging
Recorder - From 1/2 cycle RMS to 2-hour RMS
envelopes are provided. Most useful in quickly determining relay
operation by recording the RMS value of each cycle and displaying the
entire trend when breaker clears, resets, lockout or fails to operate;
up to 20 pre-fault cycles; programmable post fault on any internal and
external trigger condition. |
|
Programmable
Controller – Advanced programmable logic
makes it ideal for controlling multiple CAP banks, Tap changes under
load and alarming. Programmable 32 setpoints control, OR/AND logic,
operate with release triggers, thresholds with delays, relay control,
event-driven data recording. |
|
Digital Power Meter
- You can now eliminate the added cost of a
multifunction digital meter. Protection relays are poor substitutes for
metering and can be dangerous and misleading when high harmonic
contents are present in AC current or voltages typically found in
distribution circuits. Providing high accuracy True RMS values for
volts, amps, powers, power factors, unbalance, harmonic, demands
(predicted, fixed and sliding) and neutral current are included.
|
|
Revenue Accurate
Billing – Meets ANSII C12.2 (0.2 class)
Advanced Time-of Use feature for any complex billing scheme is
provided. Totalizing from multiple energy and demand registers from
energy pulses via external watt-meters. |
|
Directional
Harmonic Analyzer - Total Harmonic
Distortion for V&I and up to the 63rd. Including
directional power harmonics (Load or Source), power factor, phasor
diagram, symmetrical components. |
|
External Time Synchronization - provides 1 mSec time resolution
via IRIG-B time-code input or GOES type satellite clock. |
|
Dual Independent Power Supplies – Primary AC/DC and Secondary power
supply provide continuous operation. |
|
Memory Expansion Card – The SATEC SA300 can be
equipped with a 64/128-MByte Expansion Memory plug-in module
for long-term waveform and data, trend recording. |
|
AC/DC Inputs
The
SA300 is provided with a set of
fully isolated AC/DC inputs for a connection to the AC feeders and
station battery: |
|
|
Four 5.5 kV Galvanically Isolated AC
voltage inputs - Up
to 690VAC direct input voltage. |
|
Four Galvanically Isolated AC current
inputs - Includes an extended input range up
to ×3000% overload (10A/IEC or 20A/ANSI input currents, to 150
Amps fault currents). |
|
A second set of four Galvanically
Isolated current inputs (Model SA330 only) - In addition to the high
measurement CT above this additional set of CT inputs (10A/IEC or
20A/ANSI input currents) is used for precise energy metering thus eliminating expensive revenue billing meters.
|
|
DC voltage input - Used for station battery monitoring (up to 300VDC). Set point
triggers and alarming. |
Digital and Analog
I/O Options
The SA300 has five
I/O expansion slots for removable plug-in I/O modules: |
|
|
DI - Digital inputs - 16 optically isolated inputs per
module (one provided), up to 3 modules per device; options for dry
contacts, 12V, 24V, 48V and 125V wet inputs; programmable de-bounce
time from 1 ms to 1 sec; quick linkage to Sequence-of-Events Recorder,
Fault Recorder, control setpoints, pulse counters and Energy/TOU
subsystem. |
|
RO – 8 Relay Outputs - 6 Form A relays rated at 5 Amps
@125VDC and two Form C relays for energy pulsing are provided per
module. Up to 4 modules per device; programmed forunlatched, latched
and pulse operations, failsafe operation for alarm notifications;
programmable pulse width; direct remote relay control through
communications. |
|
AI/AO - Four
optically isolated analog outputs and four optically isolated inputs
internal power supplies per module. Up to 4 modules per device; options
for 0-1mA, ±1mA, 0-20mA and 4-20mA inputs and outputs;
×200% overload current for 0-1mA and ±1mA AI/AO.
|
Communications
Options
The SATEC SA300
includes FIVE independent communication ports expandable to SEVEN:
|
|
|
Three universal serial communications
ports - Com
1 = (selectable RS-232, RS-422/RS-485) COM 2 = (RS-422/RS-485),
additional RS-485 port for remote display or external RTU. Independent
selectable up to 115,200 bps (includes Modbus RTU/ASCII and DNP3.0
protocols). |
|
USB 1.1 port – 12 Mbps for fast local
communications and data retrieving |
|
Ethernet 10Base-T port - Modbus/TCP and DNP3.0/TCP
protocols, up to five non-intrusive simultaneous connections, Telnet
service port. |
|
Embedded 56K modem (optional) - for communications through public
telephone lines (Modbus RTU/ASCII and DNP3.0 protocols). |
|
Infrared port (optional) - (Modbus RTU/ASCII and DNP3.0
protocols). |
|
Auto Alarm messages to Pager or E-mail (notification of priority
problems via dial-out modem or Ethernet) – coming soon.
|
Remote Displays
The SA300 can be ordered with an optional bright LED Remote
Display Module (RDM). It has a RS485 port and communicate with
the SA300 through the Modbus RTU protocol. Remote display can
be located at distances of up to 0.5 km from the device.
The RDM300 has three six-digit windows with bright red LEDs
well suited for direct sunlight applications. It allows the user to
view real-time RMS and harmonics measurements, status indication
parameters, and perform basic setup operations when installing and
servicing the device.
Device
Models
The ezPACTM
SA300 Series production line includes two device models
|
|
SA320 - Power Quality model - offers all the ezPACTM
metering, control, and fault and event recording capabilities. Adds an
EN50160 and IEEE 1159 power quality recorder classifications and
reports, and also EN50160 statistic acquisition and reports.
|
|
SA330 - Premium model – Includes the standard 150A
current inputs for fault recording and adds to above additional four
current inputs (10A/20A) for revenue energy metering and management. |